What is a variable speed drive (VSD)?

In theory variable speed drive (VSD) is able to reduce the motor starting current at very low values is a fact that motor has limitations. I have seen many motors to stall because someone limited the starting current to a very low value. That low value is an argument to sell the equipment. Limiting the starting current depends on the type of motor and load operation curve reflected at motor shaft, for example a pumping system has a different curve than a conveyor and each application needs different starting torque and current.

At startup, a motor's backEMF is (near) zero, so a Direct-On-Line start causes a large current to flow (up to 6x rated). As current translates into torque, this also gives high starting torque.

However, in cases where such a high starting current is undesirable (such as high powered motors), the current can be reduced in two basic ways. The first is to increase the impedance, achieved using resistors in series with the motor during startup, switching them out during normal operation to maintain efficiency. The second is to reduce the applied voltage to the motor, i.e. star/delta startup.

An alternate approach is to actively regulate the current into the motor, which is what a motor drive does. It uses controlled switches (thyristors, IGBTs, etc.) to manage the flow of current into the motor, which gives it the ability to limit startup current. However, as torque is still directly related to current, the starting torque must also be affected.

All variable speed drives have soft starting as an inherent feature & thus they will definitely reduce the starting kick of motors.

And, variable speed drives will reduce current requirement of motors provided the load is less. But, that could happen without drives even. What variable frequency drive do is energy conservation, if the process flow requirements are variable.

But while you can use a variable speed drive to soft start a motor, it's expensive compared to a solid state starter if you intend to run the load a full speed all the time and there is no need for flow or speed control. A solid state starter achieves the same current limit and reduced water hammer effects by controlling just the voltage to the motor, typically using thyristors. Many soft starters have a contactor that bypasses the thyristor bridge once the motor gets to full speed.

One essential difference between a soft starter and a variable frequency drive in this regard is, that the variable speed drive delivers "nearly" sinusoidal voltages (and currents) to the motor, which makes it possible to develop high starting torques during the acceleration, even higher than nominal full load torque, depending on the application, while a soft starter only supplies fractions of the basic waveform, which serves to reduce the current to the motor significantly, but still at the nominal frequency. This will reduce the available starting torque dramatically until the motor is up to around two-thirds of nominal speed, or maybe even higher.
There is very advanced version of this which is called a cycloconverter, but that is even more expensive than a variable speed drive.

You may also like:

Theoretically a system that is based VSD should have the right to be named servo system just when it has a feedback system that is connected to the load. I've read a lot of comments were the word servo is ...
As far as running two cables for reliability, the problem is that the failure of one parallel set of conductors reduces the available current to the motor, preventing it from starting. If you are seeking ...
When select the CT ratio of 50/1 A for 6.6 kV drives where the SC rating of system is 40 kA, 50 protection may not operate because of CT saturation. Again, if the CT is not saturated, the relay terminal may ...
With the continuous improvement of the technical level of textile machinery mechatronics, variable speed control has become a trend. Most textile machines apply variable speed drives in the AC induction motors.
How to measure or diagnose common mode voltage of three phase PWM variable speed drive? And how to solve EMI from motor Driver? For your first question: Could you let me know your definition of variable ...
service VSD blog: A deep observation of automation control industry, especially in AC motor variable speed drive for industrial motor controls.

Hot Tags

Featured

7 months back I was involved in a harmonics evaluation study at Budweiser. This was one of many I've participated in over the past 20 years, basically because in facilities like ... Most of variable speed drives are applying on high temperature fans, kiln head coal mill fans, kiln head surplus fans, raw mill circulating fans and so on. Two production lines ... Variable speed drive application in purification system optimizes the system performance, improves purification effect, reduces power consumption greatly. According to related ... The motor power factor does not make a big difference other than giving an idea of loading. In regards to the variable speed drive fixing power factor everyone is mostly correct. ... A soft starter is a basic device which will ramp up the speed of your motor to full speed over a preset time, easing mechanical stress and also easing the high inrush currents ...